Add the nameplate amps (or watts) of everything on the same breaker. The bar compares the total with a 15 A or 20 A rating. It's arithmetic, not a verdict on whether an appliance may share that circuit.

    Type each value from the appliance's nameplate (the label on the back or bottom). Use its amps if it lists them. Watts are converted at 120 V, which gives the lowest current it could draw; the real current can be higher. An average or yearly energy figure is not a nameplate value, so don't use it here.

    0 A12 A, 80%15 A

    –

    Nothing entered yet. Add each appliance on the same breaker.

    The arithmetic, without the tool

    • US household outlets run at 120 V nominal (reference). Volts × amps gives volt-amperes (VA); an AC appliance's real watts can be lower, depending on its power factor. That's why the tool prefers nameplate amps.
    • A 15 A breaker at 120 V is rated for 1,800 VA, a 20 A breaker for 2,400 VA.
    • Add the watts of everything on that breaker, not just that outlet. One breaker often feeds several outlets.
    • The electrical code calls a load whose maximum current is expected to run for 3 hours or more "continuous". The usual sizing is 125% of the continuous part plus the rest, which works out to keeping continuous loads to 80% of the breaker: 12 A on 15 A, 16 A on 20 A. Exceptions and equipment rules apply (NEC 210.20(A), explained). Staying plugged in for hours doesn't by itself make an appliance a continuous load.
    • An appliance's manual can require its own circuit or outlet whatever the arithmetic says. Midea's window unit says not to share its outlet; the MRCOOL and Pioneer mini splits are hardwired on their own circuit.
    • Don't use an average or yearly-energy figure here. Rheem's 440 W for its shared-circuit water heater is an average, not its maximum.

    To find out which outlets share a breaker, or to add a circuit, ask a licensed electrician. Never swap a breaker for a bigger one to stop it tripping.

    Which outlet do you have?

    NEMA 5-15 outlet: two straight vertical slots and a round ground hole
    NEMA 5-15R15 A · 1,800 VA at 120 V
    NEMA 5-20 outlet: one slot has a sideways T
    NEMA 5-20R20 A · 2,400 VA at 120 V

    From the NEMA connector reference: a 5-20R's T-shaped slot also accepts a 15 A plug.